Sc (B) Cast Resin Dry Type Transformer (SC(B)10-200)

Application: Power, Electronic, Instrument, Lighting, Rectifier, Audio
Phase: Three
Core: Core-type Transformer
Cooling Method: Dry-type Transformer
Winding Type: Two-winding Transformer
Usage: Power
Customization:
Diamond Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
SC(B)10-200
Coil Number
Three-Phase Two-Winding
Coil Structure
Toroidal
Packaging Details
Sea Worthy Packing
Transport Package
Sea Worthy Packing
Specification
CE, ROHS, SGS, GMP
Trademark
EACHER
Origin
Zhejiang, China (Mainland)
Production Capacity
50, 000 PCS/Year

Product Description

SC(B) Cast resin Dry Type Transformer
1)Low loss and low noise
2)highly withstands short-circuit and lightning impact


Application Of Products
Our SC(B) series epoxy resin cast dry transformer is cast under vacuum with thin insulating bands automatically. The core is made of high-permeable grain-orientated silicon sheet and cast with imported epoxy resin. Thanks to advanced technology, quality raw materials, scientific management, and perfect inspection means, our products have the following features:
The coil is reinforced with glass fiber and cast under vacuum with filler epoxy resin. It has good mechanical properties, is free of crack and inner bubble and has low local discharge, high reliability, and long service life.
The high-and low-voltage systems are cast under vacuum, thus the coil will not absorb moisture; The clamps of core are subjected to corrosion-resistant treatment and it may run under high temperature or other serious environments.
Flame retardancy, explosion-proof and no environmental contamination. The insulating materials in the coil such as glass fiber are self-extinguishing and they will not cause fire by the arc resulted from short-circuit. The resin will not generate toxic or harmful gas under high temperature.
Gas duct is embedded inside it to enhance the radiation power and over-load capacity.
Low loss and low noise. The core is lapped with 45 full-miter and the step-type lamination effectively improves distribution of magnetic flux at core corners, and greatly reduces the no-load loss and the nose level.
It highly withstands short-circuit and lightning impact.
Small in volume, light in weight, safe in running and free of maintenance.
As per users' requirements the transformer may be provided with casing and blower fan.
Main Technical Parameters for 10kV SC(B) -30-2500 type
 Rated Power (kVA)  High Voltage (kV)  H.V. Tap Range  Low Voltage (kV) Connection Symbol   Short-Circuit Impedance (%)  No-Load Loss (W)   On-Load Loss (W)    No-Load Current  (%) Insulation Class  Noise (dB)  Weight (kg)  Overall Dimension L*W*H  (mm)
 50  20/22/24    ±5%  or   ±2*5% 0.4   Yyn0    Dyn11  6  340  1240 2.4   F  2.4 560   1080*660*830
 100  20/22/24     ±5%  or   ±2*5%   0.4    Yyn0    Dyn11  6    540  2000 2.2     F  2.2  690  1160*760*900
160    20/22/24    ±5%  or   ±2*5%   0.4     Yyn0    Dyn11    6   680   2470 1.8   F    1.8  810 1190*760*950 
 200   20/22/24     ±5%  or   ±2*5%   0.4    Yyn0    Dyn11  6    740  2950  1.8   F  1.8  1030  1200*760*990
 250   20/22/24     ±5%  or   ±2*5%   0.4    Yyn0    Dyn11   6  850 3420   1.6   F  1.6  1280  1220*760*1160
 315   20/22/24     ±5%  or   ±2*5%  0.4     Yyn0    Dyn11     6 970   4090 1.6    F  1.6  1530  1250*760*1210
 400   20/22/24     ±5%  or   ±2*5%   0.4    Yyn0    Dyn11  6    1150  4850  1.4   F  1.4  1660  1390*920*1470
 500   20/22/24     ±5%  or   ±2*5%   0.4   Yyn0    Dyn11     6  1350  5800 1.4   F   1.4   2010  1420*920*1360
 630   20/22/24     ±5%  or   ±2*5%   0.4    Yyn0    Dyn11   6  1530  6840 1.2    F  1.2 2390   1510*920*1460
 800   20/22/24     ±5%  or   ±2*5%  0.4      Yyn0    Dyn11   6 1760   8270  1.2   F 1.2   3060  1660*920*1510
 1000   20/22/24     ±5%  or   ±2*5%   0.4   Yyn0    Dyn11     6  2070 9790   1.0   F  1.0  3410  1740*960*1660
 1250   20/22/24     ±5%  or   ±2*5%  0.4      Yyn0    Dyn11  6    2390  11540  1.0   F  1.0     4010 1930*960*1760 
 1600  20/22/24     ±5%  or   ±2*5%  0.4      Yyn0    Dyn11   6  2790  13870  1.0  F     1.0  5030  2040*960*1960
 2000   20/22/24     ±5%  or   ±2*5%   0.4    Yyn0    Dyn11   6  3240  16390  0.8   F  0.8  5980  2040*1255*2030
 2500   20/22/24     ±5%  or   ±2*5%  0.4     Yyn0    Dyn11     6  3870  19380  0.8  F    0.8 6160   2060*1255*2200
Certifications
Sc (B) Cast Resin Dry Type Transformer (SC(B)10-200)

Certificates owned by shenda:
100MVA/220kv power transformer short circuit test report
-issued by CESI Italy&CTQC China

120MVA/33KV oil EAF transformer
50MVA/69KV oil power transformer
10MVA/33kv dry-type transformer
Type test report
-issued by KEMA Netherlands

63MVA/110KV Power transformer short circuit test report
-issued by CTQC China

12.5MVA/22KV Rectifier transformer routine test
-issued by V-Check korea

ISO 9001&ISO14001&OHSAS 18001
CE-POWER TRANSFORMER&FURNACE TRANSFORMER&DRY-TYPE TRANSFORMER&REACTOR

Transformer Characteristics
Sc (B) Cast Resin Dry Type Transformer (SC(B)10-200)
Winding .
The winding must be especially protected - both against high electrical stress due to
external over voltages and against mechanical overloads by short circuits. They are made of copper or aluminum. Low-voltage windings are made of strip or flat wire while
high voltage windings are manufactured from round or profile wire. ("diamond-dotted paper") bonds the winding into a compact block
while drying and increases the short-circuit capacity additionally.

Sc (B) Cast Resin Dry Type Transformer (SC(B)10-200)
Magnetic Core lamination.
The three-limb iron core is made of oblique cut Grain-oriented, seven-step silicon steel lamination insulated on both sides,
guaranteeing low losses and low noise. These values are even improved by laser treatment. It is protected on the surface with a
flash-proof varnish in order to prevent the sheet from corrosion and to reduce the noise.

Sc (B) Cast Resin Dry Type Transformer (SC(B)10-200)
Oil tank.
Whether during transport or operation -the tank must be absolutely tight under mechanical stress. We have vast constructional experience, the most modern calculation methods and high-quality welding work. Special attention is paid to
corrosion protection. Pretreatment of the surface is processed by phosphating pickling, contributes to corrosion protection, just
like multi-coating with preset drying times for each layer. On request, hot-dip galvanization provides for even better protection

Sc (B) Cast Resin Dry Type Transformer (SC(B)10-200)
Test lab
Testing are conducted for every transformer before delivery.Tests are classified to be routine tests and type test.
A - Routine tests: According to IEC 60076 standard , the following tests must be carried out for all units of the transformers
a- Measurement of winding resistance .
b- Measurement of voltage ratio and check of phase displacement.
c- Measurement of short circuit impedance and load losses.
d-Measurement of no-load losses and current .
e-Dielectric routine tests including the separate source AC voltage withstanding test and short duration induced over voltage withstanding test ( ACSD ) .

B - Type tests :
The following tests shall be carried out
a- Temperature rise test
b- Lightning impulse test

C - Special tests :
a- Determination of noise level according to IEC 60551 .
b- Oil leakage test
c- Overload test at 150 % rated current for one hour after temperature rise test ( top oil temperature rise and winding temperature rise must be measured and recorded in the report test also hot spot temperature rise must be calculated and recorded on the report test ) .
d- Short Circuit Dynamic stability Test (test report from independent and accredited laboratory for similar transformer will be accepted).


Packaging and transportation
Sc (B) Cast Resin Dry Type Transformer (SC(B)10-200)



Company Introduction
SHENDA electric group is a manufacturer and wholesale company that manufactures good & high quality electric transformers from 2000. The company provides the customized products and OEM service. The factory own the 3 production base worldwide,2 in China and 1 in USA.We also own a transformer research institute with more than 30 electric engineers .
Sc (B) Cast Resin Dry Type Transformer (SC(B)10-200)
Our Services
1. Pre-Sale Service
- Quick response: reply you within 8 hours, to save your time.
- Professional solution: supply professional completed solution base on your technical requirements,  to complete your technical plan.
- Quoataion: submit a competive price within 2 days, to promote your business

2. In Sale Service
- Supplying stipulated completed drawings
- Supplying manufacturing plan and processing photos
- Making the test plan and book hotel for the witness person
- Making good arrangement of the delivery and shipment

3. Afer Sale Service
- Supplying professional supervision and commissioning within 15 days
- Training the workers
- Providing 12 months waranty of quality and perforance

Sc (B) Cast Resin Dry Type Transformer (SC(B)10-200)

RFQ
1,Q:
Are you manufacturer?
 
   A:
Yes, we are manufacturer. Our factory is in JiangShan City, zhejiang  Province.
 
2,Q:
What is your delivery time ? 
 
   A:
Depend on the type of transformer.
 
3,Q:
What is your payment term?
 
  A:
30% advance by T/T , 70% before delivery by T/T or L/C or we can discuss about it.
 
4,Q:
Are your transformers supported for customization ?
 
  A:
Yes, of course. We can design and produce accroding to the technical requirements and parameters of customers.
 
5,Q:
Do you offer guarantee for the products?
 
   A:
Yes. Different transformers is different. We offer at least one year guarantee for all of our transformers.
 
6,Q:
Do you accept Factory Acceptance Test?
 
   A:
Yes. It's available. And we are responsible for each set transformer's testing (ICE).
 
7,Q:
Do you assign engineer for after-sale service?
 
   A:
Yes. For our products,we all provide after-sale installation instructions service
 
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory
Number of Employees
26
Year of Establishment
2007-11-07