220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power Transformer

Product Details
Customization: Available
Application: Power
Phase: Three

360° Virtual Tour

Diamond Member Since 2013

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
26
Year of Establishment
2007-11-07
  • 220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power Transformer
Find Similar Products

Basic Info.

Model NO.
SZ-63mva/220kv
Core
Core-type Transformer
Cooling Method
Oil-immersed Type Transformer
Winding Type
Two-winding Transformer
Certification
ISO9001-2000, ISO9001
Usage
Power Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Kou Type
Brand
Eacher
Service Condition
Indoor/Outdoor
Tap Changer
Nltc/Oltc
Cooling Type
Ofwf/Onan
Core Structure
Toroidal
High Voltage Range
220-242kv
Iron Core
Silicon Sheet
Loss
Low Loss
Transport Package
Sea Worthy Packing
Specification
CE, ISO, IEC, GB, ANSI
Trademark
EACHER
Origin
Jiangshan City, Zhejiang Province, China
Production Capacity
6000sets Per Year

Product Description

220kv 63mva three phase two winding on-load-tap-changing power transformer

Specifications
1 power transformer
2 ISO9001,ISO14001,OHSAS 18001, CE
3 Apply for IEC, ANSI
4.KEMA

Features:
1) Amount of local discharged: The apparent discharge amount is less than 80pC under 1.5 times of rated voltage;
2) Noise: Products of 63MVA and below is lower than 58 dB (AN);
3) Power loss: no-load loss is 30% lower than that of IEC standard;
4) Reliability: All in-service products have no damages or oil leakage occurred;

Application:
60 ~220 kV power system of power plant, substation, mining enterprise and etc.

Technologies:
Design: relative developed software are adopted in Electromagnetic calculations, strength analysis, leakage magnetic distribution, its electro-dynamic force and electrical insulation.

Manufacture:
Core: effectively upgrade transformer's no-load performance by below methods:
1) The core is made of high-permeable grain-orientated top quality cold-rolled silicon sheet and the material is cut with advanced Germany Geoge GmbH automatic shear line with the cut burs controlled within 0.02mm.
2) The silicon sheet fabrication adopts "no-upper yoke lapped' technology and all lapped joints of the silicon sheet are 45 full-miters. The laminated core sheets are integrally pressed and adhered with epoxy resin to make the three leg two-yoke core a strong and flat integral one with good verticality precision, this effectively improves no-load performance and reduces noises.
3) Bracing plates are used as support between coil leg and inner coil. The iron yoke is tied with epoxy resin-impregnated glass fiber band, and the lower section of oil tank is tightened with counter-pressure bolts. The upper iron and the upper section of oil tank are fixed at three locations. Hence the body inside the oil tank can withstand the vibration during transportation without any shift.

Winding:
1) The high-voltage (HV) coil adopts an interleaved-continuous structure to improve the voltage characteristics under impact voltage and make voltage evenly distributed. All stays and pads are chamfered to keep highly reliable insulation.
2) In the transformer winding there is a zigzag oil guide structure so as to fully cool all areas inside the winding, lower the temperature rise of the winding and the hot points of the winding and prolong the service life of insulation. The HV and MV regulation system are independently provided with voltage-regulating winding to balance the ampere turn of each winding, effectively lower the axial electrodynamic force generated at short-circuit of transformer and improve abrupt short-circuit withstanding capacity.
3) The winding adopts radial "0" margin designed, between the core and the paper sleeve of LV winding, and between the LV, HV, voltage-regulating windings, as well as before insertion of stays and shroud plate they are fully dried and tightly matched to ensure extremely good compactness and concentricity of the entire winding.

Oil tank and accessories
1) The tank wall adopts wide steel sheet, which will be folded into corrugated structure without splicing, in this way welds are decreased and mechanical strength is enhanced, meanwhile, the corrugated wall has diverging effect, and thus plays a role in decrease of noise. The routing troughs and control cabinets of the secondary circuit are all made of stainless steel, so the entire transformer has a simple and good looking.
2) All sealing surface use quality sealing material and are precision-machined.
3) On the edge of the tank there are double sealing grooves, and the outer sealing material is used to shade the atmosphere and ultra-ray to protect the inner sealing being damaged, thus at utmost prolonging service life and enhancing reliability of the seal.

Power transforer main Technical Parameters for 220kV power transformer Level S(F)S9, S(F)S10, S(F)S11 Serie power transformers three-phase three winding on-load-tap-changing power transformer:
 

Rated power
(kVA)

High Voltage
(kV)

H.V Tap range

Low Voltage
(kV)

Connection Symbol

Short-Circuit Impedance
(%)

No-load Loss
(kW)

On-Load Loss
(kW)

No-load Current
(%)
9 Type 10 Type 11 Type 9 Type 10 Type 11 Type
31500 220
242
±8×1.25%
±8×1.5%
6.3,6.6,
10.5,11,
20,34.5,
35,37,
38.5,66,
69
YNd11 12~14 38 34 30 135 128 128 0.7
40000 45 41 36 157 149 149 0.63
50000 54 49 43 189 180 180 0.56
63000 63 57 50 220 209 209 0.56
90000 80 72 64 288 274 274 0.49
120000 99 89 79 346 329 329 0.49
150000 116 104 93 405 385 385 0.42
180000 135 122 108 468 445 445 0.42

three-phase three winding no-load-tap-changing power transformer:

Rated power
(kVA)

High Voltage
(kV)

H.V Tap range

Low Voltage
(kV)

Connection Symbol

Short-Circuit Impedance
(%)

No-load Loss
(kW)

On-Load Loss
(kW)

No-load Current
(%)
9 Type 10 Type 11 Type 9 Type 10 Type 11 Type
31500 220
242
±8×1.25%
±8×1.5%
6.3,6.6,
10.5,11,
13.8,15.75,
18,20,
35,38.5
YNd11 12~14 35 32 28 135 128 128 0.7
40000 41 37 33 157 149 149 0.7
50000 49 44 39 189 180 180 0.65
63000 58 52 46 220 209 209 0.65
90000 77 69 62 288 274 274 0.55
120000 94 85 75 345 328 328 0.55
150000 112 101 90 405 385 385 0.5
180000 128 115 102 459 436 436 0.46
Transformer accessories
220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power Transformer

Test lab
220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power Transformer220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power Transformer
Certifications
220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power TransformerPackaging and transportation
220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power Transformer

Part of equipment
220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power Transformer


Testing center
220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power Transformer


Customer visiting
220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power Transformer

Company Introduction
SHENDA electric group is a manufacturer and wholesale company that manufactures good & high quality electric transformers from 2000. The company provides the customized products and OEM service. The factory own the 3 production base worldwide,2 in China and 1 in USA.We also own a transformer research institute with more than 30 electric engineers .
220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power Transformer220kv 63mva Three Phase Two Winding on-Load-Tap-Changing Power Transformer

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier