110kV, 121kV series power transformer & Electrical transformer
High voltage power transformer
Features:
1) Amount of local discharged: The apparent discharge amount is less than 80pC under 1.5 times of rated voltage;
2) Noise: Products of 63MVA and below is lower than 58 dB (AN);
3) Power loss: No-load loss is 30% lower than that of IEC standard;
4) Reliability: All in-service products have no damages or oil leakage occurred;
Technologies:
Design: Relative developed software are adopted in Electromagnetic calculations, strength analysis, leakage magnetic distribution, its electro-dynamic force and electrical insulation.
Manufacture:
Core: Effectively upgrade transformer's no-load performance by below methods:
1) The core is made of high-permeable grain-orientated top quality cold-rolled silicon sheet and the material is cut with advanced Germany Geoge GmbH automatic shear line with the cut burs controlled within 0.02mm.
2) The silicon sheet fabrication adopts "no-upper yoke lapped' technology and all lapped joints of the silicon sheet are 45 full-miters. The laminated core sheets are integrally pressed and adhered with epoxy resin to make the three leg two-yoke core a strong and flat integral one with good verticality precision, this effectively improves no-load performance and reduces noises.
3) Bracing plates are used as support between coil leg and inner coil. The iron yoke is tied with epoxy resin-impregnated glass fiber band, and the lower section of oil tank is tightened with counter-pressure bolts. The upper iron and the upper section of oil tank are fixed at three locations. Hence the body inside the oil tank can withstand the vibration during transportation without any shift.
Winding:
1) The high-voltage (HV) coil adopts an interleaved-continuous structure to improve the voltage characteristics under impact voltage and make voltage evenly distributed. All stays and pads are chamfered to keep highly reliable insulation.
2) In the transformer winding there is a zigzag oil guide structure so as to fully cool all areas inside the winding, lower the temperature rise of the winding and the hot points of the winding and prolong the service life of insulation. The HV and MV regulation system are independently provided with voltage-regulating winding to balance the ampere turn of each winding, effectively lower the axial electrodynamic force generated at short-circuit of transformer and improve abrupt short-circuit withstanding capacity.
3) Bracing plates are used as support between coil leg and inner coil. The iron yoke is tied with epoxy resin-impregnated glass fiber band, and the lower section of oil tank is tightened with counter-pressure bolts. The upper iron and the upper section of oil tank are fixed at three locations. Hence the body inside the oil tank can withstand the vibration during transportation without any shift.
Winding:
1) The high-voltage (HV) coil adopts an interleaved-continuous structure to improve the voltage characteristics under impact voltage and make voltage evenly distributed. All stays and pads are chamfered to keep highly reliable insulation.
2) In the transformer winding there is a zigzag oil guide structure so as to fully cool all areas inside the winding, lower the temperature rise of the winding and the hot points of the winding and prolong the service life of insulation. The HV and MV regulation system are independently provided with voltage-regulating winding to balance the ampere turn of each winding, effectively lower the axial electrodynamic force generated at short-circuit of transformer and improve abrupt short-circuit withstanding capacity.
Rated power (kVA) |
H.V (kV) |
H.V. Tap range |
L.V (kV) |
Vector Group |
Impedance (%) |
No-load Loss (kW) |
On-load Loss (kW) |
No-load Current (%) |
Oil Weight (kg) |
Total weight (kg) |
Overall dimension (mm) |
800 |
35/38.5 |
±3*2.5% |
6.3 |
Yd11 or YNd11 |
6.5 |
1.06 |
9.98 |
1.05 |
1650 |
4790 |
2870*1810*2570 |
1000 |
35/38.5 |
±3*2.5% |
6.3 |
Yd11 or YNd11 |
6.5 |
1.26 |
12.16 |
1 |
1760 |
5210 |
3150*1890*2650 |
1250 |
35/38.5 |
±3*2.5% |
6.3 |
Yd11 or YNd11 |
6.5 |
1.49 |
14.63 |
0.9 |
2010 |
6080 |
3510*2040*2690 |
1600 |
35/38.5 |
±3*2.5% |
6.3 |
Yd11 or YNd11 |
6.5 |
1.8 |
17.58 |
0.85 |
1920 |
6610 |
3560*2070*2740 |
2000 |
35/38.5 |
±3*2.5% |
6.3 |
Yd11 or YNd11 |
6.5 |
2.3 |
19.24 |
0.8 |
2160 |
7440 |
3680*2050*2850 |
2500 |
35/38.5 |
±3*2.5% |
6.3 |
Yd11 or YNd11 |
6.5 |
2.72 |
20.64 |
0.8 |
2580 |
8240 |
3780*2220*2890 |
3150 |
35/38.5 |
±3*2.5% |
6.3 |
Yd11 or YNd11 |
7 |
3.23 |
24.71 |
0.72 |
2680 |
8540 |
3850*2310*2950 |
4000 |
35/38.5 |
±3*2.5% |
6.6 |
Yd11 or YNd11 |
7 |
3.87 |
29.16 |
0.72 |
2960 |
11180 |
4120*2380*3150 |
5000 |
35/38.5 |
±3*2.5% |
10 |
Yd11 or YNd11 |
7 |
4.64 |
34.2 |
0.68 |
3050 |
12480 |
4210*2510*3220 |
6300 |
35/38.5 |
±3*2.5% |
10.5 |
Yd11 or YNd11 |
7.5 |
5.63 |
36.77 |
0.68 |
4050 |
15900 |
4320*3000*3290 |
8000 |
35/38.5 |
±3*2.5% |
11 |
Yd11 or YNd11 |
7.5 |
7.87 |
40.61 |
0.6 |
4200 |
17130 |
4500*3100*3680 |
10000 |
35/38.5 |
±3*2.5% |
11 |
Yd11 or YNd11 |
7.5 |
9.28 |
48.05 |
0.6 |
7480 |
25230 |
4560*3500*3750 |
12500 |
35/38.5 |
±3*2.5% |
11 |
Yd11 or YNd11 |
8 |
10.94 |
56.86 |
0.56 |
8010 |
27000 |
4590*3580*3830 |
16000 |
35/38.5 |
±3*2.5% |
11 |
Yd11 or YNd11 |
8 |
13.17 |
70.32 |
0.54 |
8560 |
32500 |
4650*3700*4000 |
20000 |
35/38.5 |
±3*2.5% |
11 |
Yd11 or YNd11 |
8 |
15.57 |
82.78 |
0.54 |
10030 |
37770 |
5200*4200*4280 |
25000 |
35/38.5 |
±3*2.5% |
11 |
Yd11 or YNd11 |
8 |
18.96 |
101.65 |
0.5 |
12300 |
42600 |
5320*4350*4340 |
31500 |
35/38.5 |
±3*2.5% |
11 |
Yd11 or YNd11 |
8 |
22 |
119.7 |
0.45 |
13500 |
51100 |
5450*4420*4450 |
``` |
``` |
``` |
``` |
``` |
``` |
``` |
``` |
``` |
``` |
``` |
``` |
Transformer accessories
Test lab
Certifications
Packaging and transportation
Part of equipment
Testing center
Customer visiting
Company Introduction
SHENDA electric group is a manufacturer and wholesale company that manufactures good & high quality electric transformers from 2000. The company provides the customized products and OEM service. The factory own the 3 production base worldwide,2 in China and 1 in USA.We also own a transformer research institute with more than 30 electric engineers .